Ensuring service continuity and the safety of your measurement and automation systems requires rigorous monitoring of your surge protection devices. During your maintenance rounds, the PARATRONIC GR 800 ramp tester will allow you to instantly assess the condition of your surge arresters.

 

Thunderstorm clouds—risk of lightning

Thunderstorm clouds—risk of lightning

Do your surge protectors still provide optimal protection for your equipment?

Check the voltage readings displayed by the GR 800 ramp tester in the table below. Compare them with the breakdown voltages of both new and end-of-life units of your surge arresters.

Surge arresters have a degree of aging, which can be tested using the GR 800 Tester.

 

Minimum static ignition voltages for surge arresters

  • MC = common mode (between a wire and ground)
  • MD = differential mode (between two active wires)

 

Check theminimum static ignition voltages of your surge arrester

How do I use the GR 800 tester?

What is the GR 800 used for?

The GR 800 surge arrester tester actively helps prevent risks caused by aging or degradation of internal protective components such as varistors, diodes, or spark gaps. Regular use of this device ensures optimal safety on site and prevents intermittent or catastrophic failures.

The GR 800 accurately measures the static trigger voltage of a surge arrester by applying a DC voltage ramp to it. Designed for universal use, it is compatible with PARATRONIC surge arresters but also works with most other brands on the market.

Step-by-step procedure for testing your surge arresters with the GR800:

To run your diagnostic test safely, follow these instructions.

 

1. Turning off the power:

Be sure to turn off the power to the component being tested and disconnect the surge protector from the system to avoid skewing the measurement or damaging other equipment.

 

2 Connection 

Connect the GR 800 leads directly to the terminals of the surge arrester being tested.

 

3 Measure 

Press the "ON" pushbutton to generate the DC voltage ramp.

 

4 Reading

The voltage reading (conduction or trigger voltage) automatically stabilizes on the screen.

 

5 Validation

The “VALID” LED lights up as soon as a forward current of 1 mA is detected. All you have to do is compare the value displayed on the screen with the minimum static breakdown voltages listed in our manufacturer’s tables.

 

Understanding Indicator Lights 
  • The indicator light turns on: The measurement is validated (1 mA current reached, usable voltage value).
  • The indicator light remains off: This means that the component's static trigger voltage exceeds the device's maximum measurement range (greater than 1,000 V).

 

Status Alerts and Preventive Maintenance

As a reminder, the GR 800 mobile tester perfectly complements the fixed remote monitoring systems at your facilities. In fact, some of our fixed protection devices already feature a built-in status indication system using an LED or a dry contact for status reporting (such as our flagship models PRO CEM5010AC, PRO TAS5016A(D), or PRO…).

The GR 800 is used as a supplement during your audits or physical inspections to precisely test components that have not yet triggered a visual or remote alert.

Need to test the degree of aging in your surge arresters?

Our technical sales representatives will advise you on selecting options and configuring your relay thresholds.

To receive a personalized assessment or a quote within 24 hours, please feel free to contact us.

 

News

Follow our news feed

Le Progrès. Ain Economy News. PARATRONIC sensors at the heart of environmental issues
Water cycle
Monitoring of water in the natural environment
Fire monitoring
lightning protection / lightning risk
Landslide

Ain Department. PARATRONIC Sensors at the Heart of Environmental Challenges

PARATRONIC, an SME based in the Ain region specializing in high-tech sensors, is establishing itself as a key player in the ecological transition, from Vigicrue river monitoring to forest fire detection. From lightning protection to artificial intelligence for fire prevention: focus on the Reyrieux-based company that monitors 3,500 rivers and 400,000 hectares of forest in France.

Image of the PARATRONIC cameras installed for the SDIS du 72 in the Sarthe region.
Monitoring of water in the natural environment
Fire monitoring

Environmental risks: what prevention, detection and warning systems are needed?

Large engineering firms need to rely on specialized sensor suppliers such as PARATRONIC, one of the leading players in the market, with sensors designed to detect high water, flooding, low water, dry water tables and forest fires. Patrice Rilly CEO PARATRONIC talks to Smart City mag.

risk of lightning, lightning arrester
lightning protection / lightning risk

How to Test Your Surge Protector Voltages Using the GR 800 Ramp Tester

The GR 800 surge arrester tester measures the static breakdown voltage of your surge arresters. Compatible with PARATRONIC and most other brands, it’s easy to use in just 5 steps to ensure the safety of your installations. An essential tool to complement your remote monitoring system for audits and preventive maintenance.